SMG2000E Digital Dual-Clamp Phase Volt-Ampere Meter
Contact Info
- Add:武汉市东湖开发区高新四路40号, Zip: 430074
- Contact: 蔡先生
- Tel:+8613871491300
- Email:whnort@163.com
Other Products
Product Introduction
This instrument is a high-precision, low-cost, handheld, dual-channel input measuring device specifically designed for on-site measurement of voltage, current, and phase. It can conveniently measure the phase between U-U, I-I, and U-I in the field, identify inductive and capacitive circuits, determine the phase sequence of three-phase voltages, inspect transformer wiring groups, test secondary circuits and busbar protection systems, read the phase relationship between CTs in differential protection groups, and check the correctness of watt-hour meter wiring. It uses a clamp-type current transformer to input the measured current, allowing measurements without disconnecting the circuit. When measuring the phase between U1-U2, the two input circuits are completely insulated and isolated, thereby fully avoiding potential short circuits caused by miswiring and preventing damage to the instrument. The display features a high-contrast LCD screen with characters up to 25mm high, and the screen angle can be freely adjusted by approximately 70° for optimal visual effect.
The instrument housing is made of engineering insulating material and comes with a rubber anti-vibration protective cover, ensuring safety and reliability.
Product Features
☆、Withstand Voltage: Between the voltage input terminals and the instrument case, and between the clamp-type current transformer (current clamp) core and the clamp handle and secondary winding coil, it can withstand 1000V/50Hz; between the two voltage input terminals, it can withstand 500V/50Hz sine wave AC voltage for 1 minute.
☆、Insulation Resistance: Between the digital dual-clamp phase volt-ampere meter circuit and the case, and between the two voltage input terminals: ≥10MΩ
Technical Parameters
Reference Operating Conditions
| Ambient Temperature | (23±5)℃ |
| Ambient Humidity | (45~75)% RH |
| Measured Signal Waveform | Sine wave, β=0.02 |
| Measured Signal Frequency | (50±0.2)Hz |
| Position of Measured Conductor in Clamp Jaw | Arbitrary |
| Amplitude Range for Phase Measurement | 100~220V、0.5~1.5A |
| External Reference Frequency Electromagnetic Interference | Should be avoided |
AC Voltage Measurement Error
| Range | Resolution | Basic Error Limit |
| 20V | 0.01V | ±(1.2%RD+2) |
| 200V | 0.1V | ±(1.0%RD+2) |
| 500V | 1V | ±(1.2%RD+2) |
Rated Operating Conditions
| Ambient Temperature | (0~40)℃ | |
| Ambient Humidity | (20~80)% RH | |
| Measured Signal Waveform | Sine wave, β=0.05 | |
| Measured Signal Frequency | (50±0.5)Hz | |
| Position of Measured Conductor in Clamp Jaw | Arbitrary | |
| Amplitude Range for Phase Measurement | When measuring U1-U2 phase: 30V~500V | |
| When measuring I1-I2 phase: 10mA~10.00A | ||
| When measuring U1-I2 or I1-U2 phase: 10V~500V、10mA~10.00A | ||
| External Reference Frequency Electromagnetic Interference | Should be avoided | |
| Rated Operating Error Limit | Under the above rated operating conditions, the rated operating error limit for each measurement does not exceed twice the corresponding basic error limit | |
Power Frequency Phase Measurement Error (Input Impedance for U1-U2 Phase Measurement: 40KΩ)
| Range | Resolution | Basic Error Limit |
| 0~360° | 1° | ±3° |
Other Technical Specifications
| Display Digits | 3½ digits | |
| Sampling Rate | 3 times/second | |
| Power Supply | Single 9V laminated battery, power current less than 5mA | |
| Dimensions | Case Size | 192×95×55mm3 |
| Clamp Size | 140×42×20mm3 | |
| Jaw Size | Φ7mm×9mm | |
| Weight | Main Unit | 280g |
| Measuring Clamp | 2×200g | |
| Storage Conditions | Temperature | -10℃~50℃ |
| Industry Category | Measurement-Analysis-Instruments |
|---|---|
| Product Category | |
| Brand: | 武汉诺顿whnort |
| Spec: | SMG2000E |
| Stock: | 100 |
| Manufacturer: | |
| Origin: | China / Hubei / Wuhanshi |